Skip to content
P-SHW-S Serisi
Water Cooled Chillers

P-SHW-S Serisi

Model P-SHW-S

The P-SHW-S Series comprises water-cooled water chillers with hermetic scroll compressors. Condenser heat is rejected through a cooling tower or dry cooler, giving higher efficiency and quieter running than an air-cooled equivalent. Performance is rated at 30 °C condenser inlet water. Uses environmentally friendly R 407 C refrigerant.

Cooling capacity
16 – 116,4 kW
Refrigerant
R 407 C
Technical data

Select a model

Performance figures, dimensions and the datasheet for every model in the series.

Technical specifications — P 041 SHW-S
Number of compressors pcs 1
Refrigeration circuits pcs 1
Capacity control % 0-%100
Required evaporator water flow m³/h 3
Required condenser water flow m³/h 7
Pump power (at 3 bar) kW 0,75
Tank volume L 80
L mm 950
W mm 600
H mm 1235
Water inlet connection " 1
Water outlet connection " 1
Weight kg 200
Cooling capacity kW 16
Cooling capacity kcal/h 13.767
Total compressor power kW 2,4
Cooling capacity kW 11,6
Cooling capacity kcal/h 9.981
Total compressor power kW 2,3

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 041 SHW-S — Technical drawing
Technical specifications — P 071 SHW-S
Number of compressors pcs 1
Refrigeration circuits pcs 1
Capacity control % 0-%100
Required evaporator water flow m³/h 5
Required condenser water flow m³/h 10
Pump power (at 3 bar) kW 1,5
Tank volume L 80
L mm 950
W mm 600
H mm 1235
Water inlet connection " 1
Water outlet connection " 1
Weight kg 350
Cooling capacity kW 26,8
Cooling capacity kcal/h 23.059
Total compressor power kW 4,1
Cooling capacity kW 20,1
Cooling capacity kcal/h 17.294
Total compressor power kW 3,9

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 071 SHW-S — Technical drawing
Technical specifications — P 081 SHW-S
Number of compressors pcs 1
Refrigeration circuits pcs 1
Capacity control % 0-%100
Required evaporator water flow m³/h 6
Required condenser water flow m³/h 15
Pump power (at 3 bar) kW 1,5
Tank volume L 100
L mm 1000
W mm 650
H mm 1335
Water inlet connection " 1 1/2
Water outlet connection " 1 1/2
Weight kg 400
Cooling capacity kW 34
Cooling capacity kcal/h 29.254
Total compressor power kW 5,1
Cooling capacity kW 24,4
Cooling capacity kcal/h 20.994
Total compressor power kW 5

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 081 SHW-S — Technical drawing
Technical specifications — P 101 SHW-S
Number of compressors pcs 1
Refrigeration circuits pcs 1
Capacity control % 0-%100
Required evaporator water flow m³/h 7
Required condenser water flow m³/h 30
Pump power (at 3 bar) kW 2,2
Tank volume L 100
L mm 1000
W mm 650
H mm 1335
Water inlet connection " 1 1/2
Water outlet connection " 1 1/2
Weight kg 410
Cooling capacity kW 41,6
Cooling capacity kcal/h 35.793
Total compressor power kW 6,5
Cooling capacity kW 30,1
Cooling capacity kcal/h 25.889
Total compressor power kW 5,9

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 101 SHW-S — Technical drawing
Technical specifications — P 121 SHW-S
Number of compressors pcs 1
Refrigeration circuits pcs 1
Capacity control % 0-%100
Required evaporator water flow m³/h 8
Required condenser water flow m³/h 40
Pump power (at 3 bar) kW 2,2
Tank volume L 100
L mm 1000
W mm 650
H mm 1335
Water inlet connection " 1 1/2
Water outlet connection " 1 1/2
Weight kg 430
Cooling capacity kW 49,4
Cooling capacity kcal/h 42.505
Total compressor power kW 7,3
Cooling capacity kW 35,8
Cooling capacity kcal/h 30.803
Total compressor power kW 7,1

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 121 SHW-S — Technical drawing
Technical specifications — P 151 SHW-S
Number of compressors pcs 1
Refrigeration circuits pcs 1
Capacity control % 0-%100
Required evaporator water flow m³/h 10
Required condenser water flow m³/h 50
Pump power (at 3 bar) kW 2,2
Tank volume L 120
L mm 1200
W mm 650
H mm 1335
Water inlet connection " 1 1/2
Water outlet connection " 1 1/2
Weight kg 460
Cooling capacity kW 58,2
Cooling capacity kcal/h 50.076
Total compressor power kW 11,2
Cooling capacity kW 43,4
Cooling capacity kcal/h 37.342
Total compressor power kW 11

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 151 SHW-S — Technical drawing
Technical specifications — P 072 SHW-S
Number of compressors pcs 2
Refrigeration circuits pcs 2
Capacity control % %50 - %100
Required evaporator water flow m³/h 9
Required condenser water flow m³/h 20
Pump power (at 3 bar) kW 2,2
Tank volume L 120
L mm 1200
W mm 800
H mm 1335
Water inlet connection " 2
Water outlet connection " 2
Weight kg 500
Cooling capacity kW 53,6
Cooling capacity kcal/h 46.119
Total compressor power kW 8,2
Cooling capacity kW 40,2
Cooling capacity kcal/h 34.589
Total compressor power kW 7,8

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 072 SHW-S — Technical drawing
Technical specifications — P 082 SHW-S
Number of compressors pcs 2
Refrigeration circuits pcs 2
Capacity control % %50 - %100
Required evaporator water flow m³/h 12
Required condenser water flow m³/h 30
Pump power (at 3 bar) kW 3
Tank volume L 160
L mm 1200
W mm 800
H mm 1335
Water inlet connection " 2
Water outlet connection " 2
Weight kg 580
Cooling capacity kW 68
Cooling capacity kcal/h 58.509
Total compressor power kW 10,2
Cooling capacity kW 48,8
Cooling capacity kcal/h 41.989
Total compressor power kW 10

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 082 SHW-S — Technical drawing
Technical specifications — P 102 SHW-S
Number of compressors pcs 2
Refrigeration circuits pcs 2
Capacity control % %50 - %100
Required evaporator water flow m³/h 14
Required condenser water flow m³/h 60
Pump power (at 3 bar) kW 3
Tank volume L 180
L mm 1400
W mm 900
H mm 1600
Water inlet connection " 2 1/2
Water outlet connection " 2 1/2
Weight kg 620
Cooling capacity kW 83,2
Cooling capacity kcal/h 71.587
Total compressor power kW 13
Cooling capacity kW 60,2
Cooling capacity kcal/h 51.797
Total compressor power kW 11,8

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 102 SHW-S — Technical drawing
Technical specifications — P 122 SHW-S
Number of compressors pcs 2
Refrigeration circuits pcs 2
Capacity control % %50 - %100
Required evaporator water flow m³/h 17
Required condenser water flow m³/h 80
Pump power (at 3 bar) kW 4
Tank volume L 200
L mm 1400
W mm 900
H mm 1600
Water inlet connection " 2 1/2
Water outlet connection " 2 1/2
Weight kg 640
Cooling capacity kW 98,8
Cooling capacity kcal/h 85.010
Total compressor power kW 14,6
Cooling capacity kW 71,6
Cooling capacity kcal/h 61.606
Total compressor power kW 14,2

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 122 SHW-S — Technical drawing
Technical specifications — P 152 SHW-S
Number of compressors pcs 2
Refrigeration circuits pcs 2
Capacity control % %50 - %100
Required evaporator water flow m³/h 20
Required condenser water flow m³/h 100
Pump power (at 3 bar) kW 4
Tank volume L 220
L mm 1600
W mm 1100
H mm 1600
Water inlet connection " 2 1/2
Water outlet connection " 2 1/2
Weight kg 700
Cooling capacity kW 116,4
Cooling capacity kcal/h 100.153
Total compressor power kW 22,4
Cooling capacity kW 86,8
Cooling capacity kcal/h 74.685
Total compressor power kW 22

Specifications are indicative. Final performance is confirmed at design selection.

Technical drawing

P 152 SHW-S — Technical drawing

Key features

Technical specifications

Cooling capacity 16 – 116,4 kW
Refrigerant R 407 C

Specifications are indicative. Final performance is confirmed at design selection.

Related

You may also consider

P-SHW-V Serisi
Water Cooled Chillers

P-SHW-V Serisi

Water-cooled water chiller with screw compressors.

Need help sizing the P-SHW-S Serisi?

Send us your cooling load, fluid temperatures and ambient conditions — we'll confirm the right configuration for your process.